Panel Instruments

TRIP AMPLIFIER

TX 100

TX 100

Product Description

TX-100 Trip Amplifier is a compact single-input, dual-trip output device designed for reliable process monitoring and protection in industrial applications. It supports universal inputs including RTD, thermocouple, current (4–20 mA), and voltage signals, ensuring high application flexibility. The unit provides isolated analog output (4–20 mA or 0–5 V) along with two potential-free relay trip outputs for alarm or control action. A bright 4-digit red LED display offers clear indication of process values and engineering units. With high isolation of 1.5 kV, fast response time, and DIN rail mounting, it ensures safe and dependable operation. Optional RS-485 MODBUS RTU communication enables seamless integration with automation systems.

 

Product Parameters

Configure the transmitter and electronics based on application, environment, and compliance requirements.

  Performance Characteristics           

No. of Input

01 No.

No. of Output

02 Nos.

Type of Input

Universal

1) RTD (PT-100 / PT-200 / CU-53) 2 or 3 Wire

2) Thermocouple (J / K / R / S / T / E/ B Type Thermocouple)

3) Current (0-20 mA / 4-20 mA)

4) Voltage (0-5 V DC / 0-10 V DC/1-5V DC)

Type of Output

4-20 mA / 0-5 V, Isolated

Trip Output

Potential free Relay Contacts (1 c/o, 1 Amp.)

Display

4 X 1 Digit, 0.3”, 7 Segment Red LED

Isolation

1.5 KV between Input, Output & Power Supply

Power Supply

24 V DC, External

Accuracy

Better than ± 0.25% of F. S.

Power Consumption

< 15 VA

Response Time

< 100 mSec

Temperature Coefficient

± 0.01% per °C

Enclosure

ABS, Plastic

Dimensions

75mm(H) X 55mm(W) X 110mm(D)

Mounting

Din Rail Type

Weight

500 gms

Operating Conditions

Temperature -20 to 70 °C / Humidity 5 to 95% non condensing

Temperature Drift

0.01% of F. S. / °C

Range

programmable for mA and voltage(-999 to 9999) & Fixed for RTD & thermocouple input.

OPTIONAL

 

Retransmission Output

4-20 mA / 0-5 V, Isolated

Communication Port

RS 485 supporting MODBUS RTU Protocol

Note: This product is meant for laboratory/Process application only and not for custody transfer application.

Need more technical details?

Download the complete product catalogue for detailed specifications, dimensions, certifications, and application guidance.

Applications

Electronet instruments are widely deployed across multiple industries and utilities for reliable monitoring and control of critical process parameters.

IndustryKey Applications (TX 100)
Water & Wastewater TreatmentDirect hardware pump trip on low wet well level (dry-run prevention), high-pressure pipeline surge cutoff, and intake valve closure on overflow alarm thresholds.
Automation & ManufacturingEmergency machine shutdown on hydraulic over-pressure, coolant thermal runaway interlocks, and critical bearing over-temperature trip protection on stamping/milling lines.
Oil & Gas / PetrochemicalIndependent safety trip alarms for high-high level in hydrocarbon knock-out drums, fuel pump discharge over-pressure isolation, and lube-oil failure trips on gas compressors.
Nuclear Power & Power GenerationDedicated hardware trip interlocks for boiler steam drum high/low level trips, turbine bearing over-temperature trips, and generator lube oil low-pressure trip relays.
Textile IndustryHigh-temperature emergency gas shutoff trips on stenter drying frames, over-pressure relief interlocks on yarn steaming kiers, and batch liquid level limit switching.
Pulp & Paper IndustryDryer roll steam cylinder over-pressure trip protection, pulp chest overflow/underflow prevention alarms, and chemical recovery boiler safety interlocks.
OEM Equipment ManufacturersStandard safety trip module integration into packaged boiler burner management panels, industrial chiller high/low pressure cutoffs, and compressor safety packages.
Sugar & Distillery IndustryBoiler feed line low-pressure trip protection, evaporator calandria high-pressure steam trips, and fermentation vessel over-temperature alarm interlocks.

Key Features

Core capabilities and advantages of the product.

  • Single Input, Dual Output
  • Signal Conversion with Isolation
  • Universal Input
  • 24 V DC Operated
  • RS-485 MODBUS RTU Communication
  • Din Rail Mount
  • Potential free relay outputs 2 Nos.
  • Easy Maintenance
Send Enquiry