ELMAG-100 Insertion Type Electromagnetic Flow Meter is a microcontroller-based solution designed for accurate flow measurement of conductive liquids and slurries in closed pipelines. Built on Faraday’s Law with advanced pulsed DC excitation technology, it delivers stable and reliable measurements even in challenging industrial environments. The obstruction-less insertion design ensures low pressure loss, zero maintenance, and cost-effective installation without pipeline shutdown. ELMAG-100 supports large pipe sizes from 200 NB to 3000 NB, making it ideal for water, wastewater, and process industries. It offers high accuracy up to ±1% of full scale, with outputs including 4–20 mA, pulse, HART, and RS485 (Modbus RTU) communication. Available in fixed inline and hot-retractable versions, the meter is suitable for continuous operation and harsh field conditions. With IP67/IP68 protection and multiple power options, ELMAG-100 ensures long-term performance and dependable flow monitoring.
Configure the transmitter and electronics based on application, environment, and compliance requirements.
| Model Type | 1) Mains Operated / 24V DC 2) Two wire 3) Battery Operated |
| Media | Liquid (Conductive ) |
| Conductivity | > 5 μS/cm |
| Viscosity | 200 cp max |
| Line Size | Line Size 200 NB to 3000 NB |
| Excitation | Pulsed DC |
| Display | LCD
Display - 6 Digit for Flow Rate, 8 Digit for Totalizer Flow & 4 Digit for Pressure |
| Calibration Range | As per requirement |
| Accuracy | < ± 1% of F.S. +(± 5mm /sec) for Velocity Range 0.5 m/s to 6 or 12 m/s |
| Linearity | +/- 1% of F.S. |
| Repeatability | +/- 0.5% F.S. |
| Temperature Coefficient | +/- 0.05% per °C |
| Type of Output | 1) 4 to 20mA DC |
| 2) 4 to 20mA DC with HART (Generic) | |
| 3) Pulse (Open Collector Type) | |
| Power Supply | 1) 90 - 250 VAC |
| 2) 24V DC (+/- 10%) | |
| 4) Solar Powered | |
| 3) Battery Operated | |
| Process Temperature | 85°C max |
| Process Pressure | 16 kg/cm2 max |
| Material of construction | 1) Electrode - SS 316L, Hastelloy C, Platinum, Tantalum, Titanium |
| 2) Retractable Assembly - MS / SS 316 | |
| 3) Wetted Parts - SS 316 | |
| Material of construction - Flange | SS 316 |
| Material of construction - Sensor Rod | SS 316 |
| Power Consumption | < 10 VA |
| Response Time | < 2 Sec for TX 200 and TX 600 Transmitter & <10 sec for TX 22 Transmitter |
| Electronic Protection Class | Field Mount Weather Proof IP-67, Flameproof (CMRI IIA IIB Certified) |
| Sensor / Flow Tube Protection class | Weather Proof IP-67, IP-68 |
| Process Connections | 2" ASA150 flanged |
| Mounting | Insertion type |
| Ambient Conditions | Temperature -20 to 70°C / Humidity 5 to 95% non condensing |
| Communication Output (Please refer ordering code) | 1) RS-485 supporting MODBUS RTU Protocol |
| 2) GSM, GPRS, Dual SIM GPRS, Ethernet MODBUS TCP |
Download the complete product catalogue for detailed specifications, dimensions, certifications, and application guidance.
Electronet instruments are widely deployed across multiple industries and utilities for reliable monitoring and control of critical process parameters.
| Industry | Key Applications |
| Water & Wastewater | Measuring flow in pipelines, pumping stations, and treatment systems without shutting down flow |
| Chemical & Petrochemical | Monitoring conductive liquid flow in reactors, storage tanks, and pipelines |
| Food & Beverage | Flow measurement in production lines, tanks, and process liquids with hygienic or semi-hygienic applications |
| Pharmaceuticals & Biotechnology | Monitoring flow of process liquids in bioreactors, formulation, and CIP systems |
| Pulp & Paper Industry | Measuring flow of water, chemicals, and slurries in pulping and bleaching processes |
| Power Generation | Flow measurement in cooling water, boiler feedwater, and condensate pipelines |
| Marine & Shipbuilding | Conductive liquid flow measurement in fuel, water, and process pipelines |
| Metals & Mining | Flow monitoring of slurries, chemicals, and process liquids in pipelines |
| HVAC & Building Automation | Flow measurement in chilled water, heating, and cooling circuits |
| Environmental Monitoring | Measuring flow of treated water, effluents, and process discharges |
Core capabilities and advantages of the product.